TES PROVA 19/21/23 Power Harmonics and Leakage Tester

The PROVA 19/21/23 is a portable power harmonics and leakage tester offering true RMS measurements, harmonic analysis up to the 99th order, and real-time display of voltage, current, and power parameters. Ideal for detecting power disturbances, evaluating system performance, and measuring energy consumption.

  • Fast peak detection: 39 μs (50 Hz), 33 μs (60 Hz)
  • Crest factor and total harmonic distortion (THD-F) measurement
  • Programmable CT ratios (1–250)
  • Auto Power-Off: 30 minutes

Description

The PROVA 19/21/23 Power Harmonics and Leakage Tester is a high-precision instrument designed for both single-phase and balanced three-phase systems. It provides detailed analysis of voltage and current harmonics up to the 99th order, enabling accurate monitoring of power quality and energy consumption in industrial and commercial applications.

With true RMS measurements (voltage up to 600V, current up to 100A), it ensures accuracy even under non-linear loads. The device features an LCD display (4+2+2 digits) for clear visualization of voltage, current, power, and harmonic information. It logs transient events, measures active, reactive, and apparent power, energy, phase angle, and power factor, and supports programmable CT ratios from 1 to 250.

Compact and portable, the PROVA 19/21/23 operates on two 1.5V batteries, features a 30-minute auto power-off, and is suitable for field use under temperatures from -10°C to 50°C and relative humidity below 85%.

Features

  • True RMS AC voltage (up to 600V) and current (up to 100A) measurements

  • Harmonic analysis from 1st to 99th order

  • Detection and logging of swells, dips, and outages

  • Measures active, reactive, and apparent power, energy, phase angle, and power factor

  • Fast peak detection: 39 μs (50 Hz), 33 μs (60 Hz)

  • Crest factor and total harmonic distortion (THD-F) measurement

  • Programmable CT ratios (1–250)

  • Auto Power-Off: 30 minutes

Specifications

General Specifications:

Conductor Size: 30mm (approx.)
Battery Type: two 1.5V SUM-3
Display: 4+2+2 digits LCD
Range Selection: Auto
Overload Indication: OL
Power Consumption: 10 mA (approx.)
Low battery Indication:  
Auto-Power-Off: 30 minutes after power-on
Update Time: 2 times/second (display)
No. Of Samples per Period 512 (voltage or current)

256 (power)

Temperature Coefficient (18 or 28): 0.15 x (Specified Accuracy) /
Operating Temperature: -10°C to 50°C
Operating Humidity: less than 85% relative
Altitude: up to 2000M
Storage Temperature: -20°C to 60°C
Storage Humidity: less than 75% relative
Dimension: 210mm (L) x 62mm (W) x 35.6mm (H)

8.3″ (L) x 2.5″ (W) x 1.4″ (H)

Weight: 200g (battery included)
Accessories: Test leads x 1 pair,

Carrying bag x 1,

Users manual x 1,

Batteries 1.5V x 2

Option: Alligator clips

Electrical Specifications: (23℃±5℃)

AC Watt (PROVA 21, 23)  (50 or 60 Hz, PF 0.6~1, CT=1, Voltage is greater than AC 4V,

Current is greater than AC 1mA for mA range,and Current is greater than AC 0.04A for A range.

 Specification applies to continuous waveforms)

Range (PROVA 21: 0 to 30A)

Range (PROVA 23: 0 to 60A)

Resolution Accuracy of Readings
0.050 – 9.999 W 0.001W ±2% ± 0.025W
10.00 – 99.99 W 0.01W ±2% ± 0.25W
100.0 – 999.9 W 0.1W ±2% ± 2.5W
1.000 – 9.999 KW 0.001 KW ±2% ± 0.025KW
10.00 – 99.99 KW 0.01 KW ±2% ± 0.25KW
100.0 – 999.9 KW 0.1 KW ±2% ± 2.5KW
1000 – 9999 KW 1 KW ±2% ± 25KW

 

Range (PROVA 21: 30 – 50A)

Range (PROVA 23: 60 – 100A)

Resolution Accuracy
0.050 – 9.999 W 0.001W ±2% of VA ± 5dgts
10.00 – 99.99 W 0.01W ±2% of VA ± 5dgts
100.0 – 999.9 W 0.1W ±2% of VA ± 5dgts
1.000 – 9.999 KW 0.001 KW ±2% of VA ± 5dgts
10.00 – 99.99 KW 0.01 KW ±2% of VA± 5dgts
100.0 – 999.9 KW 0.1 KW ±2%of VA ± 5dgts
1000 – 9999 KW 1 KW ±2% of VA ± 5dgts

Range of CT Ratio: 1 to 250

H.P. (Horse Power)   1 H.P. = 746 W

AC Apparent Power (VA, from 0.000VA to 9999 KVA)

                                    VA = V r.m.s. x A r.m.s

AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR)

                                    VAR =√(VA²–  W²)

AC Active Energy (mWH, WH, or KWH, from 0 mWH to 999,999 KWH)

                                    WH = W * Time (in hours)

 

AC Voltage 

 (Auto Range, True RMS, Crest Factor<4, Input Impedance 10 MΩ, Max. peak value 860VDC,

and Overload Protection AC 800V)

Range Resolution Accuracy of Readings (50/60Hz)
5V – 250 V 0.1 V ±0.5% ± 5dgts
250 V – 600 V 0.1 V ±0.5% ± 5dgts

 

Range Resolution Accuracy of Readings (45-1KHz)
5V – 250 V 0.1 V ±1.5% ± 5dgts
250 V – 600 V 0.1 V ±1.5% ± 5dgts

AC Current  (Accuracy is of Reading, Auto Range, True RMS, Crest Factor<4, CT=1,

Max. peak values 880mADC for mA range, 73.5ADC for A range, Overload Protection AC 600A)

Range Resolution Accuracy of Readings (50/60Hz)
0.5 – 60mA 0.01mA ±0.5% ± 5dgts
60 – 100mA 0.01mA ±0.5% ± 50dgts
100 – 600 mA 0.1 mA ±0.5% ± 5dgts
0.05 – 3 A 0.001 A ±0.5% ± 5dgts
3 – 30 A 0.01 A ±0.5% ± 5dgts
30 – 50 A (PROVA 19, 21) 0.01 A ±1.0% ± 5dgts
30 – 100 A (PROVA 23) 0.01 A ±1.0% ± 5dgts

 

Range Resolution Accuracy of Readings (45-1KHz)
0.5 – 60mA 0.01mA ±1.5% ± 5dgts
60 – 100mA 0.01mA ±1.5% ± 50dgts
100 – 600 mA 0.1 mA ±1.5% ± 5dgts
0.05 – 3 A 0.001 A ±1.5% ± 5dgts
3 – 30 A 0.01 A ±1.5% ± 5dgts
30 – 50 A (PROVA 19, 21) 0.01 A ±1.5% ± 5dgts
30 – 100 A (PROVA 23) 0.01 A ±1.5% ± 5dgts

 Harmonics of AC Voltage in Percentage  (1 to 99th order, minimum voltage at 50 or 60 Hz is greater

than AC 80V. If the voltage is 0 at 50 or 60 Hz, all the percentage (%) display is 0.)

Range (PROVA 19, 21) Resolution Accuracy
1 – 10th 0.1 % ±1% of reading ±1%
11 – 20th 0.1 % ±5% of reading ±1%
21 – 50th 0.1 % ±15% of reading ±1%
51 – 99th 0.1 % ±35% of reading ±1%

 

Range (PROVA 23) Resolution Accuracy
1 – 10th 0.1 % ±0.7% of reading ±1%
11 – 20th 0.1 % ±2% of reading ±1%
21 – 50th (A range) 0.1 % ±5% of reading ±1%
21 – 50th (mA range) 0.1 % ±10% of reading ±1%
51 – 99th 0.1 % ±35% of reading ±1%

Harmonics of AC Voltage in Magnitude  

(1 to 99th order, minimum voltage at 50 or 60 Hz is greater than AC 80V)

Range (PROVA 19, 21) Resolution Accuracy
1 – 10th 0.1 V ±1% of reading ±7dgts
11 – 20th 0.1 V ±5% of reading ±7dgts
21 – 50th 0.1 V ±15% of reading ±7dgts
51 – 99th 0.1 V ±35% of reading ±7dgts

 

Range (PROVA 23) Resolution Accuracy
1 – 10th 0.1 V ±0.7% of reading ±7dgts
11 – 20th 0.1 V ±2% of reading ±7dgts
21 – 50th (A range) 0.1 V ±5% of reading ±7dgts
21 – 50th (mA range) 0.1 V ±10% of reading ±7dgts
51 – 99th 0.1 V ±35% of reading ±7dgts

 

Harmonics of AC Current in Percentage  
(1 to 99th order, min. current at 50 or 60 Hz is greater than 100mA for mA range, and greater than

 1A for A range. If the current is 0 at 50 or 60 Hz, all the percentage (%) display is 0)

Range (PROVA 19, 21) Resolution Accuracy
1 – 10th 0.1 % ±1% of reading ±1%
11 – 20th 0.1 % ±5% of reading ±1%
21 – 50th 0.1 % ±15% of reading ±1%
51 – 99th 0.1 % ±35% of reading ±1%

 

Range (PROVA 23) Resolution Accuracy
1 – 10th 0.1 % ±0.7% of reading ±1%
11 – 20th 0.1 % ±2% of reading ±1%
21 – 50th (A range) 0.1 % ±5% of reading ±1%
21 – 50th (mA range) 0.1 % ±10% of reading ±1%
51 – 99th 0.1 % ±35% of reading ±1%

 Harmonics of AC Current in Magnitude  (1 to 99th order, min. current at 50 or 60 Hz is greater than

100mA for mA range, and greater than 1A for A range)

Range Resolution Accuracy
1 – 10th 0.01mA /

0.1mA /

0.001A /

0.01A

reading in mA: ±1% of reading ±2mAreading in A: ±1% of reading ±0.3A
11 – 20th reading in mA: ±7% of reading ±2mAreading in A: ±7% of reading ±0.3A
21 – 50th reading in mA: ±15% of reading ±3mAreading in A: ±15% of reading ±0.3A
51 – 99th reading in mA: ±35% of reading ±3mAreading in A: ±35% of reading ±0.3A

 Power Factor (PROVA 21, 23)

(PF, ACV > 4V, AC mA > 1mA, AC A > 0.04A, Watt > 50 digits)

Range Resolution Accuracy
0.000 – 1.000 0.001

 Phase Angle (PROVA 21, 23)  (Φ, 50 or 60Hz)

Range Resolution Accuracy
-180° to 180° 0.1°
0° to 360° 0.1°

 Frequency (Hz)

Range Resolution Accuracy of Readings Allowed Input
mA (45 – 65Hz) 0.1Hz ± 0.5Hz 20mA to 1.2A
A (45 – 65Hz) 0.1Hz ± 0.5Hz 1A to 100A

Sensitivity (PROVA 19, 21): > 20mA for mA range, > 1A for A range, and > 50V

Sensitivity (PROVA 23): > 20mA for mA range, > 3A for A range, and > 50V

 

Total Harmonic Distortion 

(THD-F with respect to the first (fundamental) harmonics, min. value in the range from 45 to 65Hz is greater

than AC 80V, greater than 1A for A range, and greater than 100mA for mA range. Calculation is done

over 1 to 50th Harmonics. If the voltage or current is 0 in the range from 45 to 65Hz, all the percentage (%) display is 0)

Range (45~65Hz) (PROVA 19, 21) Resolution Accuracy
0.0 – 10.0 % 0.1% ± 2%
10.0 – 40% 0.1% ± 5% of reading ± 5%
40 – 100% 0.1% ± 10% of reading ± 10%
100 – 999.9% 0.1% ± 20% of reading

 

Range (45~65Hz) (PROVA 23) Resolution Accuracy
0.0 – 20.0 % 0.1% ± 2%
20.0 – 100% 0.1% ±3% of reading ± 5%
100 – 999.9% 0.1% ±10% of reading ±10%

 

Peak Value of AC Periodic Voltage (peak value > 10V) or AC Periodic Current 
(peak value > 10mA for mA range and peak value > 0.5A for A range) for continuous waveform except for square wave:

Range Sampling Time Accuracy of Reading
50 Hz 39 μs ± 5% ± 30 digits
60 Hz 33 μs ± 5% ± 30 digits

 Crest Factor (C.F.) of AC Voltage (peak value > 10V) or AC Current 

(peak value > 10mA for mA range and peak value > 0.5A for A range) for continuous waveform except for square wave:

Range (45~65Hz) Resolution Accuracy of Readings
1.00 – 99.99 0.01 ± 5% ± 30 digits

 