Description
The TES-3600N 3P4W Power Analyzer is a compact and portable device for accurate measurement of electrical systems in both single-phase and three-phase setups. It provides True RMS readings for voltage, current, and power, ensuring accurate measurements under complex or non-linear loads. The analyzer measures active power (KW), reactive power (KVAR), apparent power (KVA), power factor (PF), frequency, and phase angle, offering a complete view of system performance.
Equipped with data logging up to 50 sets, a backlit LCD, and four current clamp connectors, the TES-3600N allows easy monitoring, waveform visualization, and harmonic analysis. It supports RS-232/USB connection for PC integration, making it ideal for research, quality control, field maintenance, and energy monitoring. Portable and lightweight, it can be powered by batteries or AC adapter, suitable for both lab and on-site applications.
Specifications
General Specifications :
| Size |
235(L)x116(W)x54(H)mm (9.3″Lx4.6″Wx2.1″H) |
| Operating Temperature and Humidity |
0℃to 40℃ (32℉ to 104℉) R.H. < 80% non-condensing |
| Storage Temperature and Humidity |
-10℃to 60℃ (14℉to 140℉) R.H. < 70% non-condensing |
| Accessories |
© Instruction manual
© Software CD-ROM / Optical USB interface
© Deluxe carrying case
© Battery ( “AA” 1.5V x 8pcs )
© AC adaptor (110V→12V ; 220V→12V)
© 4pcs current clamp transducer (1, 2, 3, 4 cable length 3 meters) (1000A AC, jaw opening 42mm)
© 4pcs crocodiles test leads
(blue, yellow, red, black, wire length 3 meters) |
ELECTRICAL SPECIFICATIONS (23℃±5℃) :
Voltage Measurement (V) :
| Range |
Resolution |
Accuracy |
Input impedance |
Overload protection |
Nominal power system frequency |
| 999.9V |
0.1V |
±(0.3%rdg±10dgts) (>10V) |
2MΩ |
1000Vrms |
45Hz ~ 66Hz |
AC Current Trms Measurement (A) Autoranging :
| Range |
Resolution |
Accuracy(including current probe) |
Current probe output |
Overload protection |
Nominal power system frequency |
| 999.9A |
0.1A |
±(0.5%rdg±15dgts) (>10A) |
0.35mV/A |
1000Arms |
45Hz ~ 66Hz |
Active Power measurement P (KW) :
| Range |
Resolution |
Accuracy |
| 999.9KW |
0.1KW |
±1.0%rdg±20dgts |
Apparent Power measurement S (KVA) :
| Range |
Resolution |
Accuracy |
| 999.9KVA |
0.1KVA |
±1.0%rdg±20dgts |
Reactive Power measurement Q (KVAR) :
| Range |
Resolution |
Accuracy |
| 999.9KVAR |
0.1KVAR |
±1.0%rdg±20dgts |
Power Factor measurement (COSØ) :
| Range |
Resolution |
Calculated Accuracy |
| -1 ~ +1 |
0.001 |
±10dgts |
Phase angle measurement (Ø) :
| Range |
Resolution |
Calculated Accuracy |
| +180°~ 0°~ -180° |
0.1° |
±15dgts |
Frequency measurement (Hz) :
| Range |
Resolution |
Accuracy |
Measurement source |
| 60HZ |
0.1Hz |
±0.1%rdg±2dgts |
Voltage U1 > 10V |
Three Phase Sequency Detection :
| Input voltage range |
Normal phase indication |
Reverse phase indication |
Measurement source |
| 3P > 10V |
|
|
U1, U2 and U3 |
Power Energy measurement (Wh, VAh, varh) :
| Range |
Resolution |
Active power
accuracy |
Timer interval |
Timer Accuracy |
| 9.999K |
0.001K |
Wh : ±1.0%rdg±20dgts
VAh : ±1.0%rdg±20dgts
varh : ±1.0%rdg±20dgts |
1 sec |
±50ppm (25℃, 77℉) |
| 99.99K |
0.01K |
| 999.9K |
0.1K |
| 9.999M |
0.001M |
| 30.59M |
0.01M |
q Harmonic measurement (use only PC on line analyzer) :
| Order |
Accuracy |
Harmonic Source |
| 1 ~ 63 |
±3%THD |
U1, U2, U3 > 10V
I1, I2, I3 > 10A |
Waveform (use only PC on line displayed).
Select Phase A, B or C.
Select the Voltage and current waveform outputs.