TES PROVA-A1/PROVA-A3 DC/AC Clamp Meter

The PROVA-A1/PROVA-A3 DC/AC Clamp Meter offers dual display measurement for voltage, current, resistance, capacitance, and temperature. It features auto-ranging, peak/max-min hold, backlight, and a compact design ideal for switch boxes or crowded cable areas.

  • Power Source: 2 × 1.5V AA (SUM-3) batteries
  • Operating Conditions: 0–50°C, ≤85% RH
  • Compact & Portable: 190 × 66 × 36 mm, 250 g including batteries
  • Auto Power Off: 30 minutes

Description

The PROVA-A1/PROVA-A3 is a versatile DC/AC clamp meter designed for precise measurement of current, voltage, resistance, capacitance, and temperature. It supports a wide range of AC/DC currents (DC 0–400A, AC 0–400A) and voltages (DC 0–600V, AC 0–600V) with high accuracy. The meter also features true RMS AC measurement, low-pass filtering for variable frequency drives, and dual display modes for detailed readings in challenging environments.

This clamp meter provides temperature measurement via K-type thermocouples, making it suitable for electrical and HVAC applications. It includes peak, max/min, and delta functions for both voltage and current, allowing users to capture transient events effectively. The device is compact, lightweight, and includes a backlit display, which ensures visibility in low-light areas. Additionally, it comes with auto-ranging and auto power-off functions, conserving battery life while maintaining safety standards.

Features

  • Five Dual Display Modes: Hold + Average, Max + Min, ΔMax + ΔMin, Peak Max + Peak Min, Δ Peak Max + Δ Peak Min

  • Backlit LCD Display: For clear readings in dimly lit areas

  • Auto-Ranging: Measures Voltage, Current, Resistance, Capacitance, Temperature

  • AC/DC Current & Voltage Measurement: True RMS for accurate AC readings

  • Resistance & Continuity Test: 0.1Ω resolution, audible beeper

  • Capacitance Measurement: 600nF–6000μF range

  • Temperature Measurement: Supports K-type thermocouple, -40°C to 400°C (-40°F to 752°F)

  • Peak & MAX/MIN Hold Functions: Captures transient events

  • Low Power Consumption: Approx. 17 mA

  • Auto Power Off: 30 minutes to save battery

  • Included Accessories: Carrying bag, test leads, 2 AA batteries, K-type thermocouple, adapter, user manual

  • Compact & Lightweight: 190 × 66 × 36 mm, 250 g

Specifications

GENERAL SPECIFICATION:

Parameter Specification
Use Environment Indoor Use
Maximum Conductor Size Ø 25 mm (approx.)
Battery Type 2 × 1.5 V SUM-3 (equivalent to AA size)
Display 6000 counts
Range Selection Auto and Manual
Overload Indication OL
Low Battery Indication Yes
Power Consumption Approx. 17 mA
Sampling Rate 2 times/sec
Auto Power Off 30 minutes
Operating Temperature 0°C to 50°C
Operating Humidity Less than 85% RH (non-condensing)
Maximum Altitude Up to 2000 m
Storage Temperature -20°C to 60°C
Storage Humidity Less than 75% RH (non-condensing)
Dimensions (L × W × H) 190 × 66 × 36 mm
(7.5″ × 2.6″ × 1.45″)
Weight 250 g (including batteries)
Included Accessories • Carrying bag × 1
• User manual × 1
• 1.5 V batteries × 2
• Test leads × 1 pair
• K-type thermocouple × 1
• Adapter (for capacitance and K-type thermocouple) × 1

 

 

Electrical Specifications: (23℃±5℃)

DC Current

Range Resolution Accuracy Overload Protection
60 A 10mA ±1.5%±2dgts
DC 400A
0-150 A 100mA ±1.5%±2dgts
150-300 A 100mA ±2.2%±2dgts
300-400 A 100mA ±4%±2dgts

DCA Peak MAX ±400A   Accuracy + (±2%±50dgts)

AC Current  (A1: True RMS, A3: Average Sensing)

Range Resolution Accuracy Overload Protection
50/60 Hz 40 – 500Hz
60A 10mA ±1.5%±3dgts ±2.0%±4dgts AC 400A
0-150A 100mA ±1.5%±3dgts ±2.0%±4dgts
150-300A 100mA ±2.2%±3dgts ±2.5%±4dgts
300-400A 100mA 4%±3dgts 5%±4dgts

ACA Peak MAX ±400A   Accuracy + (2%±50dgts)

LPF @1KHz -3db

DC Voltage  (Overload Protection 600V)

Range Resolution Accuracy Input Impedance
60V 10 mV ±1.5%±3dgts 10MΩ
600V 100 mV

DCV Peak MAX ±600V   Accuracy + (±2%±50dgts)

AC Voltage  (A1: True RMS, A3: Average Sensing) (Input Impedance 10 MΩ)

Range Resolution Accuracy Overload Protection
50/60 Hz 40 – 1KHz
60V 10mV ±1.5%±5dgts ±2.0%±5dgts AC 600V
600V 100mV

ACV Peak MAX ±850V   Accuracy + (±2%±50dgts)

LPF @1KHz -3db 

Continuity  (Open voltage 0.4V, Overload protection AC 600V)

Range Resolution Accuracy Beeping
60-600Ω 0.1Ω ±1.0%±2dgts <30.0Ω (approx.)

 

Resistance (Ω (Open voltage 0.4V)

Range Resolution Accuracy Overload Protection
600Ω 0.1Ω ±1.5%±2dgts AC 600V
6KΩ 1Ω
60KΩ 10Ω
600KΩ 100Ω

 

Frequency (auto range)

Range (Hz) Resolution (Hz) Accuracy Sensi-tivity OverloadProtection
4-99.99 0.01 ±0.5%±0.02 V:3V/10V  A:1A/5A AC 600V

 AC400A

100.0~999.9 0.1 ±0.5%±0.2 V:2V/10V  A:1A/5A
1.000K-9.999K 10 ±0.5%±20 V:2V/10V  A:1A/5A
10.00K-99.99K 1.2K ±0.5%±2.4K V:2V/10V  A:1A/5A
100.0K-200.0K 5K ±0.5%±10K V:2V/10V  A:1A/5A

 Temperature  (for using K-Type thermocouples, °C or °F )

Range Resolution Accuracy Overload Protection
-40 – 0 °C 0.1 °C ±2.0%±2 °C AC 300V
0 – 400 °C 0.1 °C ±0.5%±2 °C
-40 – 32 °F 0.1 °F ±2%±3.6 °F
32 – 752 °F 0.1 °F ±0.5%±3.6°F

 Diode Test

Range Resolution Accuracy Overload Protection
0 – 1.999V 0.001V ±2.5%±5dgts AC 600V

 Capacitance

Range Resolution Accuracy Overload Protection
600nF 0.1nF ±2.0%±0.2 nF  

 

AC 600V

F 1nF ±2.0%±0.02μF
60μF 10nF ±2.0%±0.02μF
600μF 100nF ±2.0%±0.2μF
6000μF F ±2.5%±5μF

 