Description
The Advanced AC Power & Harmonics Analyzer delivers precise AC current and voltage measurements. It reads currents from 3 A to 3000 A and voltages from 4 V to 600 V, providing reliable results for active, reactive, and apparent power. Users can also measure phase angle (Φ) and power factor (PF) for both single-phase and balanced three-phase systems.
This analyzer offers harmonic analysis up to the 50th order and tracks total harmonic distortion (%THD). It captures peak voltage and current events with fast sampling of 33–39 μs. The device logs 32,000 transient events in its 512 KB memory, allowing engineers to monitor swell, dip, and outage events. Its 128 × 64 dot matrix LCD with backlight ensures easy reading of data. Users can connect it to a PC via USB-RS232 for logging and analysis. Lightweight and portable, it is ideal for field testing, maintenance, and calibration tasks.
Specifications
General Specifications:
| Probe Length: 6300-24 |
24 in / 610 mm |
| Minimum Bending Diameter: |
35mm |
| Connector Diameter: |
23mm |
| Cable Diameter: |
14mm |
| Cable Length from Probe to Box: |
1700mm |
| Cable Length from Box to Output: |
1700mm |
| Data Logging Memory Size: |
512K bytes |
| Maximum Transient Events: |
32000 |
| Dimension (Box): |
130 (L) x 80 (W) x 43 (H) mm
5.1” (L) x 3.1” (W) x 1.7” (H) |
| Battery Type: |
two 1.5V SUM-3 |
| Display: |
128 X 64 Dot Matrix LCD with Backlight |
| Range Selection: |
Auto |
| Overload Indication: |
OL |
| Power Consumption: |
10mA (approx) |
| Auto-Power-Off: |
15 minutes after power-on |
| LCD Update Time: |
2 times/sec. |
| No. Of Samples per Period |
512 (voltage or current); 256 (power) |
| Operating Temperature: |
-10°C to 85°C |
| Operating Humidity: |
15% to 85% RH |
| Altitude: |
up to 2000M |
| Storage Temperature: |
-20°C to 85°C |
| Storage Humidity: |
15% to 85% RH |
| Weight: |
430g (battery included) |
| Accessories: |
Test leads (red/black) x 1 set Users manual x 1
Batteries 1.5V x 2 Carrying Case x 1 Software CD x 1
Software users manual x 1
USB to RS232 cable x 1 |
Electrical Specifications: (23℃±5℃)
AC Watt
| Range |
Resolution |
Accuracy of Readings |
| > 20 V and > 30A |
< 20V or < 30A |
| 10.0 – 999.9 W |
0.1W |
±1% of Range ±0.3W |
±2% of Range |
| 1.000 – 9.999 KW |
0.001 KW |
±1% of Range ±0.003KW |
±2% of Range |
| 10.00 – 99.99 KW |
0.01 KW |
±1% of Range ±0.03KW |
±2% of Range |
| 100.0 – 999.9 KW |
0.1 KW |
±1% of Range ±0.3KW |
±2% of Range |
| 1000 – 9999 KW |
1 KW |
±1% of Range ±3KW |
±2% of Range |
AC Apparent Power (VA)
| Range |
Resolution |
Accuracy of Readings |
| > 20 V and > 30A |
<20V or < 30A |
| 10.0 – 999.9 VA |
0.1VA |
±1% of Range ±0.3VA |
±2% of Range |
| 1.000 – 9.999 KVA |
0.001 KVA |
±1% of Range ±0.003KVA |
±2% of Range |
| 10.00 – 99.99 KVA |
0.01 KVA |
±1% of Range ±0.03KVA |
±2% of Range |
| 100.0 – 999.9 KVA |
0.1 KVA |
±1% of Range ±0.3KVA |
±2% of Range |
| 1000 – 9999 KVA |
1 KVA |
±1% of Range ±3KVA |
±2% of Range |
AC Reactive Power (VAR)
| Range |
Resolution |
Accuracy of Readings |
| > 20 V and > 30A |
<20V or < 30A |
|
|
|
|
| 10.0–999.9 VAR |
0.1VAR |
±1% of Range ±0.3VAR |
±2% of Range |
| 1.000–9.999 KVAR |
0.001 KVAR |
±1% of Range ±0.003KVAR |
±2% of Range |
| 10.00–99.99 KVAR |
0.01 KVAR |
±1% of Range ±0.03KVAR |
±2% of Range |
| 100.0–999.9 KVAR |
0.1 KVAR |
±1% of Range ±0.3KVAR |
±2% of Range |
| 1000 – 9999 KVAR |
1 KVAR |
±1% of Range ±3KVAR |
±2% of Range |
Power Factor (PF)
| Range |
Resolution |
Accuracy |
| > 20V & > 30A |
< 20V or < 30A |
| 0.000 – 1.000 |
0.001 |
± 0.04 |
±0.1 |
AC Current
| Range |
Resolution |
Accuracy of Readings |
| 3A – 300.0A |
0.1A |
±1% of Range ±0.3A |
| 300.0 – 3000A |
0.1A / 1A |
±1% of Range ±3A |
AC Voltage (Overload Protection AC 800V)
| Range |
Resolution |
Accuracy of Readings |
| 4.0 V – 600.0 V |
0.1 V |
±0.5% ± 5dgts |
Harmonics of AC Voltage in Percentage
| Range |
Resolution |
Accuracy |
| 1 – 20th |
0.1% |
±2% |
| 21 – 50th |
0.1% |
4% of reading ±2.0% |
Harmonics of AC Voltage in Magnitude
| Range |
Resolution |
Accuracy |
| 1 – 20th |
0.1% |
±2% ± 0.5V |
| 21 – 50th |
0.1% |
4% of reading ±0.5V |
Harmonics of AC Current in Percentage
| Range |
Resolution |
Accuracy |
| 1 – 20th |
0.1% |
±2% |
| 21 – 50th |
0.1% |
±6% |
Harmonics of AC Current in Magnitude (True RMS < 300A)
| Range (0 – 300A) |
Resolution |
Accuracy |
| 1 – 20th |
0.1% |
±2% of range ±0.4A |
| 21 – 50th |
0.1% |
±4% of range ±0.4A |
Harmonics of AC Current in Magnitude (3000A >True RMS> 300A)
| Range |
Resolution |
Accuracy |
| 1 – 20th |
0.1% |
±2% of range ±40A |
| 21 – 50th |
0.1% |
±4% of range ±40A |
Phase Angle (Φ, V > 20V, A > 30A)
| Range |
Resolution |
Accuracy |
| -180° to 180° |
0.1° |
± 2° |
| 0° to 360° |
0.1° |
± 2° |
Total Harmonic Distortion
| Range |
Resolution |
Accuracy |
| 0.0 – 20% |
0.1% |
± 2% |
| 20 – 100% |
0.1% |
± 7% |
| 100 – 999.9 % |
0.1% |
± 11% |
Peak Value of AC Voltage (RMS value > 20V) or AC Current (RMS value > 30A)
| Range |
Sampling Time |
Accuracy of Reading |
| 50 Hz |
39 μs |
± 5% ± 50 digits |
| 60 Hz |
33 μs |
± 5% ± 50 digits |
Frequency of AC Voltage (RMS value > 20V) or AC Current (RMS value > 30A)
| Range |
Resolution |
Accuracy |
| 46 – 65 |
0.1 |
± 0.3Hz |