Phone

+603-5621 5786

Business Hour

08:30 - 17:30

TES AFLEX-6300 Graphic Power Quality Analyzer

  • Power Quality Analysis for Single and Balanced Three Phase System
  • Harmonic Analysis of Voltage and Current (1 to 50th order)
  • True RMS measurement of V with 0.5% basic accuracy
  • True RMS measurement of A with 1% of range basic accuracy
  • Graphic Waveform of Voltage and Current Graphic Phasor Diagram
  • Transient Detection and Logging of Swell, Dip, and Outage
  • Fast peak function (39μs for 50 Hz, 33μs for 60Hz)
  • Active (W, KW, HP), reactive (VAR, KVAR) and apparent (VA, KVA) power
  • Power factor (PF), phase angle (Φ), and energy (WH, KWH)
  • Measurement of balanced 3Φ Power Quality
  • Programmable VT ratio from 1 to 3000 Hold functions
  • Auto power off function in 15 minutes

Description

Electrical Specifications: (23±5)

AC Watt

 

Range Resolution Accuracy of Readings
> 20 V and > 30A < 20V or < 30A
10.0 – 999.9 W 0.1W ±1% of Range ±0.3W ±2% of Range
1.000 – 9.999 KW 0.001 KW ±1% of Range ±0.003KW ±2% of Range
10.00 – 99.99 KW 0.01 KW ±1% of Range ±0.03KW ±2% of Range
100.0 – 999.9 KW 0.1 KW ±1% of Range ±0.3KW ±2% of Range
1000 – 9999 KW 1 KW ±1% of Range ±3KW ±2% of Range

AC Apparent Power (VA)

 

Range Resolution Accuracy of Readings
> 20 V and > 30A <20V or < 30A
10.0 – 999.9 VA 0.1VA ±1% of Range ±0.3VA ±2% of Range
1.000 – 9.999 KVA 0.001 KVA ±1% of Range ±0.003KVA ±2% of Range
10.00 – 99.99 KVA 0.01 KVA ±1% of Range ±0.03KVA ±2% of Range
100.0 – 999.9 KVA 0.1 KVA ±1% of Range ±0.3KVA ±2% of Range
1000 – 9999 KVA 1 KVA ±1% of Range ±3KVA ±2% of Range

 

AC Reactive Power (VAR)

 

 

Range Resolution Accuracy of Readings
> 20 V and > 30A <20V or < 30A

 

10.0–999.9 VAR 0.1VAR ±1% of Range ±0.3VAR ±2% of Range
1.000–9.999 KVAR 0.001 KVAR ±1% of Range ±0.003KVAR ±2% of Range
10.00–99.99 KVAR 0.01 KVAR ±1% of Range ±0.03KVAR ±2% of Range
100.0–999.9 KVAR 0.1 KVAR ±1% of Range ±0.3KVAR ±2% of Range
1000 – 9999 KVAR 1 KVAR ±1% of Range ±3KVAR ±2% of Range

Power Factor (PF)

Range Resolution Accuracy
> 20V & > 30A < 20V or < 30A
0.000 – 1.000 0.001 ± 0.04 ±0.1

AC Current

Range Resolution Accuracy of Readings
3A – 300.0A 0.1A ±1% of Range ±0.3A
300.0 – 3000A 0.1A / 1A ±1% of Range ±3A

AC Voltage (Overload Protection AC 800V)

Range Resolution Accuracy of Readings
4.0 V – 600.0 V 0.1 V ±0.5% ± 5dgts

Harmonics of AC Voltage in Percentage

Range Resolution Accuracy
1 – 20th 0.1% ±2%
21 – 50th 0.1% 4% of reading ±2.0%

Harmonics of AC Voltage in Magnitude

Range Resolution Accuracy
1 – 20th 0.1% ±2% ± 0.5V
21 – 50th 0.1% 4% of reading ±0.5V

Harmonics of AC Current in Percentage

Range Resolution Accuracy
1 – 20th 0.1% ±2%
21 – 50th 0.1% ±6%

Harmonics of AC Current in Magnitude (True RMS < 300A)

Range (0 – 300A) Resolution Accuracy
1 – 20th 0.1% ±2% of range ±0.4A
21 – 50th 0.1% ±4% of range ±0.4A

Harmonics of AC Current in Magnitude (3000A >True RMS> 300A)

Range Resolution Accuracy
1 – 20th 0.1% ±2% of range ±40A
21 – 50th 0.1% ±4% of range ±40A

Phase Angle (Φ, V > 20V, A > 30A)

Range Resolution Accuracy
-180° to 180° 0.1° ± 2°
0° to 360° 0.1° ± 2°

Total Harmonic Distortion

Range Resolution Accuracy
0.0 – 20% 0.1% ± 2%
20 – 100% 0.1% ± 7%
100 – 999.9 % 0.1% ± 11%

Peak Value of AC Voltage (RMS value > 20V) or AC Current (RMS value > 30A)

Range Sampling Time Accuracy of Reading
50 Hz 39 μs ± 5% ± 50 digits
60 Hz 33 μs ± 5% ± 50 digits

Frequency of AC Voltage (RMS value > 20V) or AC Current (RMS value > 30A)

Range Resolution Accuracy
46 – 65 0.1 ± 0.3Hz

 

 

General Specifications:

Probe Length: 6300-24 24 in / 610 mm
Minimum Bending Diameter: 35mm
Connector Diameter: 23mm
Cable Diameter: 14mm
Cable Length from Probe to Box: 1700mm
Cable Length from Box to Output: 1700mm

 

Data Logging Memory Size: 512K bytes
Maximum Transient Events: 32000
Dimension (Box): 130 (L) x 80 (W) x 43 (H) mm

5.1” (L) x 3.1” (W) x 1.7” (H)

Battery Type: two 1.5V SUM-3
Display: 128 X 64 Dot Matrix LCD with Backlight
Range Selection: Auto
Overload Indication: OL
Power Consumption: 10mA (approx)
Auto-Power-Off: 15 minutes after power-on
LCD Update Time: 2 times/sec.
No. Of Samples per Period 512 (voltage or current); 256 (power)
Operating Temperature: -10°C to 85°C
Operating Humidity: 15% to 85% RH
Altitude: up to 2000M
Storage Temperature: -20°C to 85°C
Storage Humidity: 15% to 85% RH
Weight: 430g (battery included)
Accessories: Test leads (red/black) x 1 set Users manual x 1

Batteries 1.5V x 2 Carrying Case x 1 Software CD x 1

Software users manual x 1

USB to RS232 cable x 1

Ready to Transform Your Business? Contact Us Today

Categories

Request a Quote or Further Information

Please fill in the request form below and one of our engineers will contact you to discuss your system requirements and if we can help, our typical response time is within 1 – 3 working day.